Product Specs
Generator Set Specifications
- Maximum Rating
- 550 kVA
- Minimum Rating
- 365 kVA
- Emissions/Fuel Strategy
- Low Fuel, Tier 2 or 3
- Voltage
- 208 to 600 Volts
- Frequency
- 50 Hz
- Speed
- 1500 rpm
- Duty Cycle
- Standby, Prime
Engine Specifications
- Engine Model
- C15 ATAAC, I-6, 4-Stroke Water-Cooled Diesel
- Bore
- 5.4 in
- Stroke
- 6.75 in
- Displacement
- 927.56 in³
- Compression Ratio
- 16.1:1
- Aspiration
- Air to Air Aftercooled
- Fuel System
- MEUI
- Governor Type
- Adem™A4
Generator Set Dimensions
- Length - Maximum
- 222.7 in
- Width - Maximum
- 90 in
- Height - Maximum
- 93.2 in
Standard Equipment
-
- Air System
-
- Aftercooler core
- Turbocharger
- Air cleaner - Non canister disposable paper filter
-
- Air Inlet
-
- Air cleaner
-
- Control Panel
-
- GCCP 1.3
- GCCP 1.3
-
- Cooling
-
- Package mounted radiator
-
- Cooling System
-
- Radiator and cooling fan with guard
- Coolant drain line with valve
- Caterpillar extended life coolant
- Fan drive, battery charging alternator drive
-
- Fuel
-
- Secondary fuel filters
- Fuel priming pump
- Primary fuel filter with integral water separator
-
- Exhaust
-
- Stainless steel exhaust flex, gaskets, raincap & SAE exhaust flange for customer use - shipped loose
- Exhaust flange outlet
-
- Fuel System
-
- Standard open set fuel tank/base supplied
- Base, formed steel with single wall integral 8-hour fuel tank
-
- Generator
-
- IP23 Protection
- Matched to the performance and output characteristics of Cat engines
- Load adjustment module provides engine relief upon load impact and improves load acceptance and recovery time
-
- Generator And Attachments
-
- IP23 Protection
- A Frame generator - IP21 Protection
- Segregated low voltage (AC/DC) wiring panel
- Mandatory option circuit breaker, IEC, 3 pole, mounted in power centre
- Optional LC Frame generator - IP23 Protection
- Power center, IP22
- Integrated voltage regulator (IVR)
-
- Power Termination
-
- Busbar
-
- Governing System
-
- Cat electronic governor (ADEM A4)
-
- Lube System
-
- Lubricating oil
- Oil drain valves
-
- Mounting
-
- Rubber vibration isolators
-
- Mounting System
-
- Rubber vibration isolators
-
- Starting/charging
-
- 24 Volt battery with rack and cables
- Batteries
- 24 volt starting motor
-
- General
-
- Engine and alternator pre paint, Caterpillar yellow
- Paint - Caterpillar yellow except rails and radiators gloss black
Attachments
-
- Air Inlet System
-
- Single element air cleaner
- Dual element air cleaner
-
- Exhaust
-
- Industrial, residential, critical mufflers
-
- Certifications
-
- EU Certificate of Conformance (CE)
- Global certification for CIS
-
- Generator
-
- Oversize and premium generators
- Anti-condensation heater
- Excitation: [ ] Permanent magnet excitation (PMG) Excited (PM) [ ] Internally Excited (IE)
-
- Power Termination
-
- Circuit breakers, UL listed
- Circuit breakers, IEC compliant
-
- Circuit Breakers
-
- 4 Pole (IEC-100% rated) Circuit breakers - Motorised
- 3 Pole (IEC-100% rated) Circuit breakers - Motorised
- Auxiliary contacts, circuit breaker
- 4 Pole (IEC-100% rated) Circuit breakers - Package mounted
- Padlockable circuit breaker device
- Power terminal strip
- Shunt trip for IEC circuit breaker
- 3 Pole (IEC-100% rated) Circuit breakers - Package mounted
-
- Control Panels
-
- Protective devices: Earth fault relay ; Earth leakage Ground fault relay ; Overload shutdown via breaker ; Low fuel level alarm ; Low fuel level shutdown ; High fuel level alarm ; Fuel level sensor
- Remote annunciator module
- Oil temperature displays
- GCCP 1.4
- Local annunciator
- Local alarm horn
- Volt free contacts
-
- Starting/charging
-
- Jacket water heater
- Heavy duty starting system
- Battery chargers
- Oversize batteries
- Charging alternator
-
- Cooling System
-
- Radiator duct flange
- Stone guards
- Low coolant temperature alarm
-
- Enclosures
-
- Sound attenuated enclosures
- High ambient sound attenuated enclosures
-
- Exhaust System
-
- End in/end out mufflers - 10, 25 and 35 dBA attenuation
- Manifold and turbocharger guards
- Flexible exhaust fittings
- 6 and 8 inch flange GP
- 6 and 8 inch elbow kit
- Engine mounted muffler
-
- Fuel System
-
- Dual wall fuel tank base
- Manual fuel transfer pump
- Fuel transfer system controls
-
- General
-
- UL 2200 package
- Automatic transfer switches (ATS)
- Narrow, wide or skid base
- Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
- Single or dual wall sub-base fuel tanks
- EU Certificate of Conformance (CE)
- EEC Declaration of Conformity
- The following options are based on regional and product configuration:
- Single or dual wall integral fuel tanks
- CSA Certification
- Sound attenuated, weather protective or high ambient weather protective enclosure
- Integral & sub-base UL listed dual wall fuel tanks
-
- Generator And Attachments
-
- Oversize A Frame generator
- LC frame generator
- Oversize LC frame generator
- CIP A Frame generator
- LC frame CIP generator
- Permanent magnet excitation (PMG) generator
- Space heaters
- Ingress protection
-
- Lube System
-
- Manual sump pump
-
- Mounting System
-
- Narrow skid base - replaces standard fuel tank base
-
- Special Test / Reports
-
- PGS Test report @ 1.0 power factor
- PGS Test report @ 0.8 power factor
-
- Starting / Charging System
-
- 5 Amp single Battery charger
- Battery disconnect switch